Electric Radiant Floor Mat Calculator

Enter the room size, the floor area taken by cabinets, vanities, the toilet and the tub, and the mat's watt density and voltage.

Floor under cabinets, vanities, the toilet, the tub and other built-ins.
SunTouch TapeMat 120 V sizes run from 10 to 50 sq ft in 5 sq ft steps, then 60, 70 and 80 sq ft (2021 spec sheet). Mats cannot be cut to fit.
SunTouch TapeMat: 12 W/sq ft (D12 and C12 series) or 15 W/sq ft (C15 series).
Typical, editable. SunTouch's manual allows up to 12 A of mats on a 15 A breaker (80%).
SunTouch SunStat control: 15 A maximum load. Check the rating of the control you use.

Room Area

80 sq ft

Heated Area

60 sq ft

Mat Area (no larger than heated area)

60 sq ft

Heating Load

720 W

Current Draw

6 A

Allowed on One Circuit

12 A

Fits on One Circuit

Yes

Largest Mat Area on One Circuit

120 sq ft

Circuits Needed

1 circuits

How it works

Floor-warming mats go only where the floor is open. The heated area is the room's length × width minus the floor under cabinets, vanities, the toilet, the tub and other built-ins; SunTouch's TapeMat manual says never to install mats under cabinets or built-ins with no floor clearance. Mats come in fixed sizes and cannot be cut, so the mat area is the heated area rounded down to the mat size step.

The heating load is the mat area × the watt density, and the current is watts ÷ volts. At 12 W/sq ft that is 1 A per 10 sq ft at 120 V and 1 A per 20 sq ft at 240 V, which is what SunTouch's TapeMat specification sheet lists for every mat it sells.

SunTouch's TapeMat manual loads a circuit to less than its breaker rating: up to 12 A of mats on a 15 A breaker and 12–15 A on a 20 A breaker, with 15 A the most one SunStat control can switch. The calculator allows the continuous-load share of the breaker you enter (80% by default, which matches SunTouch's 12 A on 15 A) or the thermostat's own maximum, whichever is lower, and reports whether the mats fit on one circuit and how many circuits the load would need at least.

Formula

room area       = length × width
heated area     = room area − area not heated
mat area        = heated area rounded down to the mat size step
watts           = mat area × watt density
amps            = watts ÷ volts
allowed amps    = min(breaker × continuous-load limit %, thermostat rating)
fits            = amps ≤ allowed amps
largest mat     = allowed amps × volts ÷ watt density
circuits needed = amps ÷ allowed amps, rounded up (a lower bound; whole mats cannot be split)

Example

A 10 × 8 ft bathroom is 80 sq ft. Taking out 20 sq ft for the vanity, toilet and tub leaves 60 sq ft to heat, which is a 60 sq ft mat.

At 12 W/sq ft the mat draws 720 W, or 6 A at 120 V. A 15 A circuit at 80% allows 12 A, so it fits on one circuit; the largest mat area that circuit carries at 12 W/sq ft and 120 V is 120 sq ft.

Assumptions and limitations

  • The room is a rectangle and the area not heated is entered as one total.
  • Watt density is the mat's rated figure; the nameplate amp rating governs where it differs.
  • Circuits needed (amps ÷ allowed amps, rounded up) is a lower bound. Whole mats cannot be split between circuits, so the mats' sizes can require more: three 8 A mats on circuits allowing 12 A each need 3 circuits, not 2.
  • The 80% continuous-load limit and the 15 A thermostat rating are typical, editable values. SunTouch's manual uses them for its own products; other makers and controls have their own limits.
  • Only the mats are counted. Other loads on the same circuit, such as lights or an exhaust fan, are not included.
  • This is an estimate, not an electrical design or code compliance check. It is not a substitute for the mat and thermostat manufacturer's instructions, the electrical code in force where you live or a licensed electrician.

Frequently asked questions

Why is the mat area smaller than the heated area?

Mats are made in fixed sizes and cannot be cut or overlapped, so the mat that fits is the largest size that is no bigger than the open floor. SunTouch's manual also keeps mats a few inches from walls, tubs and the toilet ring, which leaves some open floor unheated.

Does 240 V let one circuit heat more floor?

Yes. The same watts draw half the current at 240 V, so at 12 W/sq ft a 15 A circuit at 80% (12 A) carries 120 sq ft at 120 V and 240 sq ft at 240 V.