Wire Resistance Calculator

100 ft of 12 AWG copper at 20 °C is 0.1588 Ω of DC resistance. Enter a size or cross-section, the material and temperature, and the length of wire.

Last reviewed

Total metal cross-section of the conductor (all strands together).
Stranding adds about 2 % for the longer path of the twisted strands.
Custom only. 1 µΩ·cm = 10⁻⁸ Ω·m.
Custom only. Enter 0 to ignore temperature.
Resistance is quoted at 20 °C in the wire tables; a loaded conductor runs warmer.
The length of conductor, not the distance to the load: a two-wire circuit has twice the run length.

Your wire's DC resistance

Resistance

158.8219 mΩ

Resistance in ohms

0.158822 Ω

The wire

solid 12 AWG copper, 100 ft

Resistance per 1,000 ft

1.58822 Ω

Resistance per km

5.21069 Ω

Cross-section

3.3088 mm²

Cross-section

6,530 cmil

Resistivity at the conductor temperature

1.7241 µΩ·cm

Conductor radius

1.0263 mm

Conductivity at 20 °C

58.001 MS/m

A solid 12 AWG copper, 100 ft run at 20 °C has a DC resistance of 0.1588 Ω.

That is 1.5882 Ω per 1,000 ft and 5.2107 Ω per km over a 3.3088 mm² (6,530 cmil) cross-section.

The copper resistivity at 20 °C is 1.7241 µΩ·cm.

Price the same run in the voltage-drop calculator. It shows the voltage left at the far end. The speaker wire-gauge calculator sizes a speaker run. The skin depth and AC resistance calculator carries the same wire into AC.

Worked sheet for Wire Resistance: how the resistance of 158.8219 mΩ is worked out, in 4 steps.Wire ResistanceR = ρ × k × L ÷ Aρ = ρ₂₀ × (1 + α × (T − 20))k = 1.02 stranded, 1 solidCross-section A = 6,530 cmil = 3.3088 mm²Resistivity ρ at 20 °C = 1.7241 µΩ·cmLength L = 30.48 mR = ρ × k × L ÷ A =158.8219 mΩ
  1. Cross-section A = 6,530 cmil = 3.3088 mm²
  2. Resistivity ρ at 20 °C = 1.7241 µΩ·cm
  3. Length L = 30.48 m
  4. R = ρ × k × L ÷ A = 158.8219 mΩ
How 0.1588 Ω for the solid 12 AWG copper, 100 ft run is worked out

Resistance against wire length

Resistance against wire length, length 10 to 1,000: the resistance rises from 0.0159 Ω to 1.5882 Ω.00.511.52102004006008001,000LengthResistanceResistance against wire length, length 10 to 1,000: the resistance rises from 0.0159 Ω to 1.5882 Ω.00.511.52105001,000LengthResistance
Across the lengths in the table the resistance rises in a straight line, from 0.0159 Ω at 10 ft to 1.5882 Ω at 1000 ft.

Resistance against temperature

Resistance against temperature, temperature (°C) 0 to 100: the resistance rises from 0.1463 Ω to 0.2088 Ω.00.10.20.3020406080100Temperature (°C)ResistanceResistance against temperature, temperature (°C) 0 to 100: the resistance rises from 0.1463 Ω to 0.2088 Ω.00.10.20.3050100Temperature (°C)Resistance
From 0 to 100 °C the resistance of 12 AWG moves from 0.1463 Ω to 0.2088 Ω, at the material's temperature coefficient.

Resistance at each length

At 10 the run measures 15.882192573386384 Ω, and at 1000 it measures 1.5882192573386382 Ω. Each row's grid gives the resistance at other conductor temperatures.

Length of wireResistance
1015.8822 mΩ
2539.7055 mΩ
5079.411 mΩ
100 (closest to your input)158.8219 mΩ
150238.2329 mΩ
200317.6439 mΩ
250397.0548 mΩ
400635.2877 mΩ
500794.1096 mΩ
1,0001.5882 Ω

Resistance for each length (rows) and conductor temperature in °C (columns).

Length of wire by conductor temperature0 °C20 °C40 °C60 °C75 °C100 °C
1014.6339 mΩ15.8822 mΩ17.1305 mΩ18.3789 mΩ19.3151 mΩ20.8756 mΩ
2536.5846 mΩ39.7055 mΩ42.8263 mΩ45.9472 mΩ48.2878 mΩ52.1889 mΩ
5073.1693 mΩ79.411 mΩ85.6527 mΩ91.8944 mΩ96.5756 mΩ104.3778 mΩ
100 (closest to your input)146.3385 mΩ158.8219 mΩ171.3053 mΩ183.7887 mΩ193.1513 mΩ208.7555 mΩ
150219.5078 mΩ238.2329 mΩ256.958 mΩ275.6831 mΩ289.7269 mΩ313.1333 mΩ
200292.677 mΩ317.6439 mΩ342.6107 mΩ367.5775 mΩ386.3026 mΩ417.5111 mΩ
250365.8463 mΩ397.0548 mΩ428.2633 mΩ459.4718 mΩ482.8782 mΩ521.8888 mΩ
400585.3541 mΩ635.2877 mΩ685.2213 mΩ735.1549 mΩ772.6051 mΩ835.0222 mΩ
500731.6926 mΩ794.1096 mΩ856.5266 mΩ918.9437 mΩ965.7564 mΩ1.0438 Ω
1,0001.4634 Ω1.5882 Ω1.7131 Ω1.8379 Ω1.9315 Ω2.0876 Ω

Resistance by wire size

SizeCircular milsArea (mm²)Ω per 1,000 ftΩ per km
4/0 AWG211,600107.2190.0490.1608
2/0 AWG133,07767.4310.07790.2557
1/0 AWG105,53553.4750.09830.3224
2 AWG66,37133.6310.15630.5127
4 AWG41,74121.1510.24850.8152
6 AWG26,25113.3020.39511.2961
8 AWG16,5108.3660.62822.0609
10 AWG10,3835.2610.99883.277
12 AWG6,5303.3091.58825.2107
14 AWG4,1072.0812.52548.2853
16 AWG2,5831.3094.015513.1742
18 AWG1,6240.8236.384920.9478
20 AWG1,0220.51810.152433.3083
22 AWG6420.32616.142952.9622
24 AWG4040.20525.668284.2132

The row for 12 AWG is the wire entered above: 1.5882 Ω per 1,000 ft and 5.2107 Ω per km at 20 °C, on a 3.3088 mm² (6,530 cmil) section.

Resistance by length

LengthResistance (Ω)
100.0159
250.0397
500.0794
1000.1588
1500.2382
2000.3176
2500.3971
4000.6353
5000.7941
1,0001.5882

Resistance by conductor temperature

Temperature (°C)Resistance (Ω)
00.1463
200.1588
400.1713
600.1838
750.1932
1000.2088

How it works

Resistance is resistivity times length, divided by the cross-section: R = ρ × L ÷ A. Double the length and the resistance doubles; double the area and it halves.

An AWG size fixes the area. The gage sets 4/0 at 0.4600 in across and 36 AWG at 0.0050 in, with 38 sizes between them in geometric progression. The diameter in inches is 0.005 × 92^((36 − n)/39). Sizes above 4/0 are named in thousands of circular mils, so 250 kcmil is 250,000 cmil. The standard resistivities at 20 °C are 1.7241 µΩ·cm for annealed copper and 2.8264 µΩ·cm for EC-H19 aluminum.

Metals conduct less well as they warm. The calculator moves the 20 °C resistivity with the material's temperature coefficient: ρ_T = ρ₂₀ × (1 + α × (T − 20)). A stranded conductor is about 2 % more resistive than a solid one of the same area.

How the result maps onto the wire tables

NBS Handbook 100 prints the sizes in the order the table above does. Its Table 5 lists each AWG size, the diameter in mils, the area in circular mils, and the resistance in ohms per thousand feet at 20 °C. Match the per-thousand-feet line here to that column. For the default case the line reads 1.5882 Ω per thousand feet, and the handbook row for 12 AWG prints 1.59.

Table 6 repeats those rows at 0, 20, 25, 50, 75, 100 and 200 °C. Its 75 °C column is the one a loaded conductor meets. The temperature grid here reads the same way: enter 75 as the conductor temperature and compare with that column. A wire reel's datasheet follows the same layout, with a resistance at 20 °C and a maximum operating temperature printed beside it.

The cross-section lines translate the table's units. The result shows circular mils and square millimeters side by side. NIST's conversion guide sets the circular mil at 5.067 075 × 10⁻⁴ mm², which turns 6,530 cmil into 3.3088 mm². The kcmil name above 4/0 is the same unit in thousands, so 250 kcmil is 250,000 cmil.

Video walkthrough

A 2½-minute walkthrough of the DC resistance a run of copper wire adds, from the length of the wire to the size, the temperature and the material.

Wire Resistance Calculator: Ohms in a Copper Run
Read the transcript

How much resistance is in this run?

0:00 Here is 100 feet of solid 12 gauge copper wire at 20 degrees Celsius.

0:06 Its resistance is about 0.16 ohms.

0:10 That is the figure the calculator shows when the page first opens.

How much wire does the run hold?

0:15 The length is the wire, not the distance to the load.

0:18 A run of 100 feet to a load holds 200 feet of copper, out and back.

0:24 So the answer doubles to about 0.32 ohms.

0:27 The worked sheet shows the same step: the length line doubles.

0:32 The answer with it doubles from about 0.16 ohms.

0:35 It lands at about 0.32 ohms.

Where does that number come from?

0:39 The answer comes from a few terms: the resistivity of the material, the length of the wire, and the cross-section of the conductor.

0:47 The worked sheet writes the first times the second, with a stranding factor k, divided by the third.

0:53 The wire size sets that cross-section, and the handbook prints this wire at about 1.59 ohms per 1,000 feet.

What does the temperature change?

1:02 The same wire reads more resistance when it runs hot.

1:05 At 0 degrees Celsius the run is about 0.15 ohms.

1:11 At 75 degrees Celsius it is about 0.19 ohms.

1:16 Here the warmer wire reads the higher figure.

1:19 The handbook lists that row across the temperatures, and the 75 degrees Celsius cell reads about 1.93 ohms per 1,000 feet.

What do the size and the metal change?

1:29 In this example, the resistance roughly halves for every 3 sizes larger.

1:34 At 9 gauge the same wire falls to about 0.08 ohms.

1:39 At 6 gauge it falls to about 0.04 ohms.

1:43 Here each thicker wire reads the lower figure.

1:46 Copper keeps the answer small; aluminum runs higher.

1:50 The same run in aluminum is about 0.26 ohms.

1:54 It runs about 1.6 times the copper figure.

1:58 For stranded wire, the handbook takes an increment of 2% in its tables.

What should you check first?

2:03 Match the temperature to the job before you trust the number.

2:07 This is an estimate of a physical property, not a code compliance decision.

2:12 Confirm the conductor size and length against the real installation.

2:16 The answer rises with length and falls as the conductor grows larger.

2:21 The length is the wire itself, not the distance to the load, and the size and temperature move the answer.

2:28 Check the volts left at the far end of the same run in the voltage-drop calculator at fastcalc.us.

Formula

d (in)  = 0.005 × 92^((36 − n) ÷ 39)    (AWG n; 1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3)
A (cmil) = (1000 × d)², or kcmil × 1000;  A (m²) = cmil × π/4 × (25.4 × 10⁻⁶ m)²
ρ_T = ρ₂₀ × (1 + α₂₀ × (T − 20 °C))
R = ρ_T × k × L ÷ A    (k = 1 solid, 1.02 stranded)

Example

Take 100 ft of solid 12 AWG copper at 20 °C. The wire is 0.0808 in across (6,529.9 cmil, 3.3088 mm²). So R = 1.7241 × 10⁻⁸ Ω·m × 30.48 m ÷ 3.3088 × 10⁻⁶ m². That is 0.1588 Ω (158.8 mΩ), or 1.5882 Ω per 1,000 ft. NBS Handbook 100, Table 5 prints 12 AWG copper at 1.59 Ω per 1,000 ft.

Take 400 ft of solid 6 AWG copper at 20 °C. The answer is 0.1580 Ω (0.3951 Ω per 1,000 ft). The table prints 0.3952 for 6 AWG, which rounds to 0.1581 Ω over 400 ft. For 200 ft of 14 AWG the answer is 0.5051 Ω (2.5254 Ω per 1,000 ft). The table prints 2.52 there because it rounds the 14 AWG diameter to 64.1 mil.

1,000 ft of solid 10 AWG copper at 75 °C is 1.2147 Ω. NBS Handbook 100, Table 6 lists 1.215 Ω there. The same wire in EC-H19 aluminum is 2.0004 Ω at 75 °C, computed from the constants in NBS Handbook 109, Table 1.

Long runs, small wires, and other cases

An extension cord is the small-wire case. A 50 ft cord of 16 AWG holds 100 ft of copper out and back, and that copper alone is 0.4015 Ω at 20 °C. A speaker wire-gauge run of the same length in 18 AWG is worse. Both sag under load, so check the drop with the voltage-drop calculator before a heater or an amplifier goes on the end.

A long low-voltage run is the heavy-current case. Wire for a 12 V array at 100 ft carries more current than 120 V work, and a small resistance wastes a larger share of the voltage. Size that conductor with the DC solar wire-size calculator. The loss itself is a wattage: the Ohm's law calculator gives it from the resistance shown here and the current the run carries.

The finest gages are the measurement case. Below 24 AWG the handbook diameters are rounded to 0.1 mil, so the printed resistance drifts a little from the exact gage definition. A four-wire measurement keeps lead resistance out of a fine-gage reading. When the reel is labeled in square millimeters, the wire-gauge conversion calculator gives the AWG match.

Assumptions and limitations

  • DC resistance only. Skin effect, proximity effect and a cable's reactance are not computed.
  • The resistivity and the temperature coefficient are the published standard values for annealed copper (NBS Handbook 100, 1966) and EC-H19 aluminum (NBS Handbook 109, 1972). Alloy, temper, purity and coating change them. Hard-drawn copper is about 2.5 % more resistive (Handbook 100). Other materials can be entered as Custom.
  • AWG areas come from the gage's definition. The handbooks tabulate diameters rounded to 0.1 mil, so their finest sizes differ a little from the exact values here.
  • Stranded conductors count as 2 % above solid, the figure Handbook 100 uses up to 2,000,000 cmil. Real stranding factors vary by class and maker.
  • Temperature correction is a straight line from the coefficient at 20 °C. Handbook 100 tabulates copper by this rule from 0 to 200 °C (Table 6). This page refuses aluminum above 100 °C. Below 0 °C the figure continues the same line. Custom materials have no upper limit.
  • This is an estimate of a physical property. It is not a code compliance decision, and it is not a substitute for the maker's data. Conductor sizing is decided under the code by a licensed electrician and the authority having jurisdiction.

These figures are calculation aids, not a code determination. Always follow the code adopted where you live, your local inspector and a licensed professional. Terms of use.

What to do with the result

Enter the length of conductor, not the distance to the load: a 100 ft run to a load holds 200 ft of wire out and back. Double the figure before you compare it with a voltage budget in the voltage-drop calculator.

Match the temperature to the job. The same 100 ft of 12 AWG copper is 0.1463 Ω at 0 °C, 0.1588 Ω at 20 °C and 0.1932 Ω at 75 °C. That is a 32 % difference between the ends. Compare with a table at 20 °C, and use a warmer figure for a loaded conductor. The resistance temperature-correction calculator carries the same step onto a measured value.

Use the size table to pick a larger wire. Every three AWG sizes halves the resistance per foot: 12 AWG at 1.588 Ω per 1,000 ft becomes about 0.79 Ω at 9 AWG and 0.40 Ω at 6 AWG. For the circuit that protects it, see the breaker-size calculator.

Frequently asked questions

How much more resistive is aluminum wire than copper of the same gauge?

At 20 °C, EC-H19 aluminum's resistivity is 2.8264 µΩ·cm against copper's 1.7241, so the same size is 1.64 times as resistive. The NBS copper table shows 10 AWG at 0.9988 Ω per 1,000 ft, which puts the aluminum conductor at 1.637 Ω.

Why does going up three gauge sizes halve the resistance?

Each AWG step multiplies the diameter by 92^(1/39) ≈ 1.1229, so three steps multiply the area by 1.1229⁶ ≈ 2.005. Twice the area is half the resistance: 10 AWG (0.9988 Ω per 1,000 ft) is near half of 13 AWG (2.00 Ω).

What is the resistance of 100 feet of 12 gauge wire?

Solid copper at 20 °C is 0.1588 Ω, or 1.588 Ω per thousand feet, which NBS Handbook 100 prints as 1.59. At 75 °C it is 0.1932 Ω; stranded copper at 20 °C is 2 % higher at 0.1620 Ω.

How does temperature change wire resistance?

Copper's resistance rises 0.393 % for every °C above 20 °C. From 20 °C to 75 °C that is 55 × 0.393 % = 21.6 %, so 1.588 Ω per 1,000 ft becomes 1.932 Ω. The handbook table lists 1.93 for that cell.

Why is my measured wire resistance different from the table?

Tables assume annealed copper at the standard resistivity, a solid conductor and 20 °C. A multimeter reading also includes lead and contact resistance, which matters when 100 ft of 12 AWG is only 0.16 Ω.

What is the resistance of a 50 ft 16 AWG extension cord?

16 AWG copper is 4.0155 Ω per 1,000 ft at 20 °C. A 50 ft cord holds 100 ft of copper out and back, so the wire alone is 0.4015 Ω. The voltage-drop calculator turns that into volts lost at the load.