Wire Resistance Calculator
100 ft of 12 AWG copper at 20 °C is 0.1588 Ω of DC resistance. Enter a size or cross-section, the material and temperature, and the length of wire.
Last reviewed
Your wire's DC resistance
Resistance
158.8219 mΩ
Resistance in ohms
0.158822 Ω
The wire
solid 12 AWG copper, 100 ft
Resistance per 1,000 ft
1.58822 Ω
Resistance per km
5.21069 Ω
Cross-section
3.3088 mm²
Cross-section
6,530 cmil
Resistivity at the conductor temperature
1.7241 µΩ·cm
Conductor radius
1.0263 mm
Conductivity at 20 °C
58.001 MS/m
A solid 12 AWG copper, 100 ft run at 20 °C has a DC resistance of 0.1588 Ω.
That is 1.5882 Ω per 1,000 ft and 5.2107 Ω per km over a 3.3088 mm² (6,530 cmil) cross-section.
The copper resistivity at 20 °C is 1.7241 µΩ·cm.
- Cross-section A = 6,530 cmil = 3.3088 mm²
- Resistivity ρ at 20 °C = 1.7241 µΩ·cm
- Length L = 30.48 m
- R = ρ × k × L ÷ A = 158.8219 mΩ
Resistance against wire length
Resistance against temperature
Resistance at each length
At 10 the run measures 15.882192573386384 Ω, and at 1000 it measures 1.5882192573386382 Ω. Each row's grid gives the resistance at other conductor temperatures.
| Length of wire | Resistance |
|---|---|
| 10 | 15.8822 mΩ |
| 25 | 39.7055 mΩ |
| 50 | 79.411 mΩ |
| 100 (closest to your input) | 158.8219 mΩ |
| 150 | 238.2329 mΩ |
| 200 | 317.6439 mΩ |
| 250 | 397.0548 mΩ |
| 400 | 635.2877 mΩ |
| 500 | 794.1096 mΩ |
| 1,000 | 1.5882 Ω |
Resistance for each length (rows) and conductor temperature in °C (columns).
| Length of wire by conductor temperature | 0 °C | 20 °C | 40 °C | 60 °C | 75 °C | 100 °C |
|---|---|---|---|---|---|---|
| 10 | 14.6339 mΩ | 15.8822 mΩ | 17.1305 mΩ | 18.3789 mΩ | 19.3151 mΩ | 20.8756 mΩ |
| 25 | 36.5846 mΩ | 39.7055 mΩ | 42.8263 mΩ | 45.9472 mΩ | 48.2878 mΩ | 52.1889 mΩ |
| 50 | 73.1693 mΩ | 79.411 mΩ | 85.6527 mΩ | 91.8944 mΩ | 96.5756 mΩ | 104.3778 mΩ |
| 100 (closest to your input) | 146.3385 mΩ | 158.8219 mΩ | 171.3053 mΩ | 183.7887 mΩ | 193.1513 mΩ | 208.7555 mΩ |
| 150 | 219.5078 mΩ | 238.2329 mΩ | 256.958 mΩ | 275.6831 mΩ | 289.7269 mΩ | 313.1333 mΩ |
| 200 | 292.677 mΩ | 317.6439 mΩ | 342.6107 mΩ | 367.5775 mΩ | 386.3026 mΩ | 417.5111 mΩ |
| 250 | 365.8463 mΩ | 397.0548 mΩ | 428.2633 mΩ | 459.4718 mΩ | 482.8782 mΩ | 521.8888 mΩ |
| 400 | 585.3541 mΩ | 635.2877 mΩ | 685.2213 mΩ | 735.1549 mΩ | 772.6051 mΩ | 835.0222 mΩ |
| 500 | 731.6926 mΩ | 794.1096 mΩ | 856.5266 mΩ | 918.9437 mΩ | 965.7564 mΩ | 1.0438 Ω |
| 1,000 | 1.4634 Ω | 1.5882 Ω | 1.7131 Ω | 1.8379 Ω | 1.9315 Ω | 2.0876 Ω |
Resistance by wire size
| Size | Circular mils | Area (mm²) | Ω per 1,000 ft | Ω per km |
|---|---|---|---|---|
| 4/0 AWG | 211,600 | 107.219 | 0.049 | 0.1608 |
| 2/0 AWG | 133,077 | 67.431 | 0.0779 | 0.2557 |
| 1/0 AWG | 105,535 | 53.475 | 0.0983 | 0.3224 |
| 2 AWG | 66,371 | 33.631 | 0.1563 | 0.5127 |
| 4 AWG | 41,741 | 21.151 | 0.2485 | 0.8152 |
| 6 AWG | 26,251 | 13.302 | 0.3951 | 1.2961 |
| 8 AWG | 16,510 | 8.366 | 0.6282 | 2.0609 |
| 10 AWG | 10,383 | 5.261 | 0.9988 | 3.277 |
| 12 AWG | 6,530 | 3.309 | 1.5882 | 5.2107 |
| 14 AWG | 4,107 | 2.081 | 2.5254 | 8.2853 |
| 16 AWG | 2,583 | 1.309 | 4.0155 | 13.1742 |
| 18 AWG | 1,624 | 0.823 | 6.3849 | 20.9478 |
| 20 AWG | 1,022 | 0.518 | 10.1524 | 33.3083 |
| 22 AWG | 642 | 0.326 | 16.1429 | 52.9622 |
| 24 AWG | 404 | 0.205 | 25.6682 | 84.2132 |
The row for 12 AWG is the wire entered above: 1.5882 Ω per 1,000 ft and 5.2107 Ω per km at 20 °C, on a 3.3088 mm² (6,530 cmil) section.
Resistance by length
| Length | Resistance (Ω) |
|---|---|
| 10 | 0.0159 |
| 25 | 0.0397 |
| 50 | 0.0794 |
| 100 | 0.1588 |
| 150 | 0.2382 |
| 200 | 0.3176 |
| 250 | 0.3971 |
| 400 | 0.6353 |
| 500 | 0.7941 |
| 1,000 | 1.5882 |
Resistance by conductor temperature
| Temperature (°C) | Resistance (Ω) |
|---|---|
| 0 | 0.1463 |
| 20 | 0.1588 |
| 40 | 0.1713 |
| 60 | 0.1838 |
| 75 | 0.1932 |
| 100 | 0.2088 |
How it works
Resistance is resistivity times length, divided by the cross-section: R = ρ × L ÷ A. Double the length and the resistance doubles; double the area and it halves.
An AWG size fixes the area. The gage sets 4/0 at 0.4600 in across and 36 AWG at 0.0050 in, with 38 sizes between them in geometric progression. The diameter in inches is 0.005 × 92^((36 − n)/39). Sizes above 4/0 are named in thousands of circular mils, so 250 kcmil is 250,000 cmil. The standard resistivities at 20 °C are 1.7241 µΩ·cm for annealed copper and 2.8264 µΩ·cm for EC-H19 aluminum.
Metals conduct less well as they warm. The calculator moves the 20 °C resistivity with the material's temperature coefficient: ρ_T = ρ₂₀ × (1 + α × (T − 20)). A stranded conductor is about 2 % more resistive than a solid one of the same area.
How the result maps onto the wire tables
NBS Handbook 100 prints the sizes in the order the table above does. Its Table 5 lists each AWG size, the diameter in mils, the area in circular mils, and the resistance in ohms per thousand feet at 20 °C. Match the per-thousand-feet line here to that column. For the default case the line reads 1.5882 Ω per thousand feet, and the handbook row for 12 AWG prints 1.59.
Table 6 repeats those rows at 0, 20, 25, 50, 75, 100 and 200 °C. Its 75 °C column is the one a loaded conductor meets. The temperature grid here reads the same way: enter 75 as the conductor temperature and compare with that column. A wire reel's datasheet follows the same layout, with a resistance at 20 °C and a maximum operating temperature printed beside it.
The cross-section lines translate the table's units. The result shows circular mils and square millimeters side by side. NIST's conversion guide sets the circular mil at 5.067 075 × 10⁻⁴ mm², which turns 6,530 cmil into 3.3088 mm². The kcmil name above 4/0 is the same unit in thousands, so 250 kcmil is 250,000 cmil.
Video walkthrough
A 2½-minute walkthrough of the DC resistance a run of copper wire adds, from the length of the wire to the size, the temperature and the material.
Read the transcript
How much resistance is in this run?
0:00 Here is 100 feet of solid 12 gauge copper wire at 20 degrees Celsius.
0:06 Its resistance is about 0.16 ohms.
0:10 That is the figure the calculator shows when the page first opens.
How much wire does the run hold?
0:15 The length is the wire, not the distance to the load.
0:18 A run of 100 feet to a load holds 200 feet of copper, out and back.
0:24 So the answer doubles to about 0.32 ohms.
0:27 The worked sheet shows the same step: the length line doubles.
0:32 The answer with it doubles from about 0.16 ohms.
0:35 It lands at about 0.32 ohms.
Where does that number come from?
0:39 The answer comes from a few terms: the resistivity of the material, the length of the wire, and the cross-section of the conductor.
0:47 The worked sheet writes the first times the second, with a stranding factor k, divided by the third.
0:53 The wire size sets that cross-section, and the handbook prints this wire at about 1.59 ohms per 1,000 feet.
What does the temperature change?
1:02 The same wire reads more resistance when it runs hot.
1:05 At 0 degrees Celsius the run is about 0.15 ohms.
1:11 At 75 degrees Celsius it is about 0.19 ohms.
1:16 Here the warmer wire reads the higher figure.
1:19 The handbook lists that row across the temperatures, and the 75 degrees Celsius cell reads about 1.93 ohms per 1,000 feet.
What do the size and the metal change?
1:29 In this example, the resistance roughly halves for every 3 sizes larger.
1:34 At 9 gauge the same wire falls to about 0.08 ohms.
1:39 At 6 gauge it falls to about 0.04 ohms.
1:43 Here each thicker wire reads the lower figure.
1:46 Copper keeps the answer small; aluminum runs higher.
1:50 The same run in aluminum is about 0.26 ohms.
1:54 It runs about 1.6 times the copper figure.
1:58 For stranded wire, the handbook takes an increment of 2% in its tables.
What should you check first?
2:03 Match the temperature to the job before you trust the number.
2:07 This is an estimate of a physical property, not a code compliance decision.
2:12 Confirm the conductor size and length against the real installation.
2:16 The answer rises with length and falls as the conductor grows larger.
2:21 The length is the wire itself, not the distance to the load, and the size and temperature move the answer.
2:28 Check the volts left at the far end of the same run in the voltage-drop calculator at fastcalc.us.
Formula
d (in) = 0.005 × 92^((36 − n) ÷ 39) (AWG n; 1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3) A (cmil) = (1000 × d)², or kcmil × 1000; A (m²) = cmil × π/4 × (25.4 × 10⁻⁶ m)² ρ_T = ρ₂₀ × (1 + α₂₀ × (T − 20 °C)) R = ρ_T × k × L ÷ A (k = 1 solid, 1.02 stranded)
Example
Take 100 ft of solid 12 AWG copper at 20 °C. The wire is 0.0808 in across (6,529.9 cmil, 3.3088 mm²). So R = 1.7241 × 10⁻⁸ Ω·m × 30.48 m ÷ 3.3088 × 10⁻⁶ m². That is 0.1588 Ω (158.8 mΩ), or 1.5882 Ω per 1,000 ft. NBS Handbook 100, Table 5 prints 12 AWG copper at 1.59 Ω per 1,000 ft.
Take 400 ft of solid 6 AWG copper at 20 °C. The answer is 0.1580 Ω (0.3951 Ω per 1,000 ft). The table prints 0.3952 for 6 AWG, which rounds to 0.1581 Ω over 400 ft. For 200 ft of 14 AWG the answer is 0.5051 Ω (2.5254 Ω per 1,000 ft). The table prints 2.52 there because it rounds the 14 AWG diameter to 64.1 mil.
1,000 ft of solid 10 AWG copper at 75 °C is 1.2147 Ω. NBS Handbook 100, Table 6 lists 1.215 Ω there. The same wire in EC-H19 aluminum is 2.0004 Ω at 75 °C, computed from the constants in NBS Handbook 109, Table 1.
Long runs, small wires, and other cases
An extension cord is the small-wire case. A 50 ft cord of 16 AWG holds 100 ft of copper out and back, and that copper alone is 0.4015 Ω at 20 °C. A speaker wire-gauge run of the same length in 18 AWG is worse. Both sag under load, so check the drop with the voltage-drop calculator before a heater or an amplifier goes on the end.
A long low-voltage run is the heavy-current case. Wire for a 12 V array at 100 ft carries more current than 120 V work, and a small resistance wastes a larger share of the voltage. Size that conductor with the DC solar wire-size calculator. The loss itself is a wattage: the Ohm's law calculator gives it from the resistance shown here and the current the run carries.
The finest gages are the measurement case. Below 24 AWG the handbook diameters are rounded to 0.1 mil, so the printed resistance drifts a little from the exact gage definition. A four-wire measurement keeps lead resistance out of a fine-gage reading. When the reel is labeled in square millimeters, the wire-gauge conversion calculator gives the AWG match.
Assumptions and limitations
- DC resistance only. Skin effect, proximity effect and a cable's reactance are not computed.
- The resistivity and the temperature coefficient are the published standard values for annealed copper (NBS Handbook 100, 1966) and EC-H19 aluminum (NBS Handbook 109, 1972). Alloy, temper, purity and coating change them. Hard-drawn copper is about 2.5 % more resistive (Handbook 100). Other materials can be entered as Custom.
- AWG areas come from the gage's definition. The handbooks tabulate diameters rounded to 0.1 mil, so their finest sizes differ a little from the exact values here.
- Stranded conductors count as 2 % above solid, the figure Handbook 100 uses up to 2,000,000 cmil. Real stranding factors vary by class and maker.
- Temperature correction is a straight line from the coefficient at 20 °C. Handbook 100 tabulates copper by this rule from 0 to 200 °C (Table 6). This page refuses aluminum above 100 °C. Below 0 °C the figure continues the same line. Custom materials have no upper limit.
- This is an estimate of a physical property. It is not a code compliance decision, and it is not a substitute for the maker's data. Conductor sizing is decided under the code by a licensed electrician and the authority having jurisdiction.
These figures are calculation aids, not a code determination. Always follow the code adopted where you live, your local inspector and a licensed professional. Terms of use.
What to do with the result
Enter the length of conductor, not the distance to the load: a 100 ft run to a load holds 200 ft of wire out and back. Double the figure before you compare it with a voltage budget in the voltage-drop calculator.
Match the temperature to the job. The same 100 ft of 12 AWG copper is 0.1463 Ω at 0 °C, 0.1588 Ω at 20 °C and 0.1932 Ω at 75 °C. That is a 32 % difference between the ends. Compare with a table at 20 °C, and use a warmer figure for a loaded conductor. The resistance temperature-correction calculator carries the same step onto a measured value.
Use the size table to pick a larger wire. Every three AWG sizes halves the resistance per foot: 12 AWG at 1.588 Ω per 1,000 ft becomes about 0.79 Ω at 9 AWG and 0.40 Ω at 6 AWG. For the circuit that protects it, see the breaker-size calculator.
Frequently asked questions
How much more resistive is aluminum wire than copper of the same gauge?
At 20 °C, EC-H19 aluminum's resistivity is 2.8264 µΩ·cm against copper's 1.7241, so the same size is 1.64 times as resistive. The NBS copper table shows 10 AWG at 0.9988 Ω per 1,000 ft, which puts the aluminum conductor at 1.637 Ω.
Why does going up three gauge sizes halve the resistance?
Each AWG step multiplies the diameter by 92^(1/39) ≈ 1.1229, so three steps multiply the area by 1.1229⁶ ≈ 2.005. Twice the area is half the resistance: 10 AWG (0.9988 Ω per 1,000 ft) is near half of 13 AWG (2.00 Ω).
What is the resistance of 100 feet of 12 gauge wire?
Solid copper at 20 °C is 0.1588 Ω, or 1.588 Ω per thousand feet, which NBS Handbook 100 prints as 1.59. At 75 °C it is 0.1932 Ω; stranded copper at 20 °C is 2 % higher at 0.1620 Ω.
How does temperature change wire resistance?
Copper's resistance rises 0.393 % for every °C above 20 °C. From 20 °C to 75 °C that is 55 × 0.393 % = 21.6 %, so 1.588 Ω per 1,000 ft becomes 1.932 Ω. The handbook table lists 1.93 for that cell.
Why is my measured wire resistance different from the table?
Tables assume annealed copper at the standard resistivity, a solid conductor and 20 °C. A multimeter reading also includes lead and contact resistance, which matters when 100 ft of 12 AWG is only 0.16 Ω.
What is the resistance of a 50 ft 16 AWG extension cord?
16 AWG copper is 4.0155 Ω per 1,000 ft at 20 °C. A 50 ft cord holds 100 ft of copper out and back, so the wire alone is 0.4015 Ω. The voltage-drop calculator turns that into volts lost at the load.
Sources
- NBS Handbook 100, Copper Wire Tables (published Feb 21, 1966)
- NBS Handbook 109, Aluminum Wire Tables (version Feb 1972)
- NIST Special Publication 811, Appendix B.8: Factors for Units Listed Alphabetically (page modified Aug 18, 2025)
More in Wiring Calculators and Electrical Calculators.